0% found this document useful (0 votes)
25 views12 pages

W3G910GV0201 Ba Eng

The document provides operating instructions for a device manufactured by ebm-papst, emphasizing the importance of safety regulations and proper use. It details various hazard warnings, staff qualifications, and basic safety rules, as well as technical data and guidelines for installation, maintenance, and disposal. The device is intended for conveying air and must be operated by qualified personnel while adhering to specified conditions to prevent hazards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
25 views12 pages

W3G910GV0201 Ba Eng

The document provides operating instructions for a device manufactured by ebm-papst, emphasizing the importance of safety regulations and proper use. It details various hazard warnings, staff qualifications, and basic safety rules, as well as technical data and guidelines for installation, maintenance, and disposal. The device is intended for conveying air and must be operated by qualified personnel while adhering to specified conditions to prevent hazards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

W3G910-GV02-01

Operating instructions

ebm-papst Mulfingen GmbH & Co. KG 1. SAFETY REGULATIONS AND NOTES


Bachmühle 2
D-74673 Mulfingen Please read these operating instructions carefully before starting to work
Phone +49 (0) 7938 81-0 with the device. Observe the following warnings to prevent malfunctions
Fax +49 (0) 7938 81-110 or physical damage to both property and people.
[email protected] These operating instructions are to be regarded as part of this device.
www.ebmpapst.com If the device is sold or transferred, the operating instructions must
accompany it.
CONTENTS These operating instructions may be duplicated and forwarded for
information about potential dangers and their prevention.
1. SAFETY REGULATIONS AND NOTES 1
1.1 Levels of hazard warnings
1.1 Levels of hazard warnings 1
These operating instructions use the following hazard levels to indicate
1.2 Staff qualification 1 potentially hazardous situations and important safety regulations:
1.3 Basic safety rules 1
DANGER
1.4 Electrical voltage 1 Indicates an imminently hazardous situation which, if not
1.5 Safety and protective functions 2 avoided, will result in death or serious injury. Compliance with
1.6 Electromagnetic radiation 2 the measures is mandatory.

1.7 Mechanical movement 2 WARNING


Indicates a potentially hazardous situation which, if not avoided,
1.8 Emission 2
could result in death or serious injury. Exercise extreme
1.9 Hot surface 2 caution while working.
1.10 Transport 2 CAUTION
1.11 Storage 2 Indicates a potentially hazardous situation which, if not avoided,
1.12 Disposal 3 may result in minor or moderate injury or damage of property.
NOTE
2. PROPER USE 3
A potentially harmful situation can occur and, if not avoided, can
3. TECHNICAL DATA 4 lead to property damage.
3.1 Product drawing 4 1.2 Staff qualification
3.2 Nominal data 5
The device may only be transported, unpacked, installed, operated,
3.3 Data according to ErP directive 5 maintained and otherwise used by qualified, trained and authorised
3.4 Technical features 5 technical staff.
Only authorised specialists are permitted to install the device, to carry
3.5 Mounting data 5
out a test run and to perform work on the electrical installation.
3.6 Transport and storage conditions 6
3.7 Electromagnetic compatibility 6 1.3 Basic safety rules
Any safety hazards stemming from the device must be re-evaluated
4. CONNECTION AND START-UP 6
once it is installed in the end device.
4.1 Connecting the mechanical system 6 Observe the following when working on the unit:
4.2 Connecting the electrical system 6
Translation of the original operating instructions

; Do not make any modifications, additions or conversions to the


4.3 Connection in terminal box 7 device without the approval of ebm-papst.
4.4 Factory settings 8
1.4 Electrical voltage
4.5 Connection screen 9
; Check the electrical equipment of the device at regular intervals, refer
4.6 Checking the connections 10 to chapter 6.2 Safety test.
4.7 Switch on device 10 ; Replace loose connections and defective cables immediately.
4.8 Switching off the device 10 WARNING
5. INTEGRATED PROTECTIVE FUNCTIONS 10 Terminals and connections have voltage even with a
unit that is shut off
6. MAINTENANCE, MALFUNCTIONS, POSSIBLE 11 Electric shock
CAUSES AND REMEDIES → Wait five minutes after disconnecting the voltage at all poles
6.1 Cleaning 12 before opening the device.
6.2 Safety test 12 CAUTION
In the event of failure, there is electric voltage at the
rotor and impeller
The rotor and impeller are base insulated.
→ Do not touch the rotor and impeller once they are installed.

Item no. 50276-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 1 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions

CAUTION WARNING
If control voltage is applied or a speed setpoint is stored, Rotating device
the motor automatically restarts, e.g. after a power failure. Long hair, loose items of clothing and jewellery could become
Danger of injury entangled and pulled into the device. You could be injured.
→ Keep out of the danger zone of the device. → Do not wear any loose clothing or jewellery while working
→ When working on the device, switch off the mains on rotating parts.
supply voltage and secure the latter from being switched on → Protect long hair by wearing a cap.
again.
→ Wait until the device stops.
1.8 Emission
→ After working on the device, remove any used tools or WARNING
other objects from the device. Depending on the installation and operating conditions,
a sound pressure level greater than 70 dB(A) may arise.
1.5 Safety and protective functions Danger of noise-induced hearing loss
DANGER → Take appropriate technical safety measures.
Missing safety device and non-functioning safety device → Protect operating personnel with appropriate safety
If there is no safety device, you could be seriously injured, for equipment, e.g. hearing protection.
example if you reach into the running device or your hands are → Also observe the requirements of local agencies.
sucked into it.
→ Operate the device only with a fixed and isolating safety 1.9 Hot surface
protection and a fixed guard grille.
CAUTION
The guard must withstand the kinetic energy of a fan blade
High temperature at the electronics enclosure
detaching at maximum speed.
Danger of burn injuries
→ The device is a built-in component. You, the owner/
→ Ensure that sufficient protection against accidental contact is
operator, are responsible for providing adequate protection for
provided.
the device.
→ Shut down the device immediately if you detect a 1.10 Transport
missing or ineffective protective feature.
WARNING
1.6 Electromagnetic radiation Transport of fan
Injuries from slipping or falling.
Interference from electromagnetic radiation is possible, e.g. in conjunction
with open and closed-loop control devices. → Only transport the fan in its original packaging. # Transport
If unacceptable emission intensities occur when the fan is installed, the fan "lying flat", in other words with the axis vertical.
appropriate shielding measures have to be taken by the user. → Secure the fan(s) so that nothing can slip or fall, for
example using a lashing strap.
NOTE
Electrical or electromagnetic interferences after 1.11 Storage
integrating the device in installations on the customer's
side. ; Store the device, partially or fully assembled, in a dry and
→ Verify that the entire setup is EMC compliant. weatherproof manner in the original packing in a clean environment.
; Protect the device from environmental impacts and dirt until the final
1.7 Mechanical movement installation.
Translation of the original operating instructions

DANGER ; We recommend storing the device for a maximum up to one year to


Rotating device guarantee proper operation and longest possible service life.
Body parts that come into contact with the rotor and impeller ; Even devices explicitly suited for outdoor use are to be stored as
can be injured. described prior to being commissioned.
→ Secure the device against accidental contact. ; Maintain the storage temperature, see
→ Before working on the system/machine, wait until all chapter 3.6 Transport and storage conditions.
parts have come to a standstill. ; Please make sure that all screwed cable glands are fitted with
dummy plugs.
DANGER
Flying parts
Missing safety devices may cause balancing weights or
broken fan blades to be ejected at high speeds, causing bodily
harm.
→ Take appropriate safety measures.

Item no. 50276-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 2 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions

1.12 Disposal 2. PROPER USE


When disposing of the device, please comply with all relevant The device is exclusively designed as a built-in device for conveying
requirements and regulations applicable in your country. air according to its technical data.
Any other usage above and beyond this does not conform with the
intended purpose and constitutes misuse of the device.
Customer equipment must be capable of withstanding the mechanical
and thermal stresses that can arise from this product. This applies for the
entire service life of the equipment in which this product is installed.
Proper use also includes:
● Use the device in power systems with earthed neutral (TN/TT power
systems) only.
● Only using the device in stationary systems.
● Carrying out all maintenance.
● Moving air with a density of 1.2 kg/m³.
● Using the device in accordance with the permitted ambient
temperature, see chapter 3.6 Transport and storage conditions and
chapter 3.2 Nominal data.
● Operating the device with all protective features in place.
● Minding the operating instructions.

Improper use
Using the device in the following ways is particularly prohibited and
may cause hazards:
● Operating the device with an imbalance, e.g. caused by dirt deposits
or icing.
● Operation in medical equipment with a life-sustaining or lifesaving
function.
● Operation with external vibrations.
● Moving solids content in flow medium.
● Painting the device
● Connections (e.g. screws) coming loose during operation.
● Opening the terminal box during operation.
● Moving air that contains abrasive particles.
● Moving highly corrosive air, e.g. salt spray mist. Exceptions are
devices that are intended for salt spray mist and protected accordingly.
● Moving air that contains dust pollution, e.g. suctioning off saw dust.
● Operating the device close to flammable materials or components.
Translation of the original operating instructions

● Operating the device in an explosive atmosphere.


● Using the device as a safety component or for taking on safety-
related functions.
● Operation with completely or partially disassembled or modified
protective features.
● In addition, all application options that are not listed under proper use.

Item no. 50276-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 3 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions

3. TECHNICAL DATA

3.1 Product drawing

All measures have the unit mm.

1 Direction of air flow "V"


2 Cable diameter: min. 4 mm, max. 10 mm, tightening torque: 4±0.6 Nm
3 Tightening torque 3.5±0.5 Nm
Translation of the original operating instructions

Item no. 50276-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 4 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions

3.2 Nominal data Humidity class F4-1


Mounting position Shaft horizontal or rotor on bottom; rotor
Motor M3G150-NA on top on request
Phase 3~ Condensate discharge Rotor-side
Nominal voltage / VAC 400 holes
Nominal voltage 380 .. 480 Operation mode S1
range / VAC Motor bearing Ball bearing
Frequency / Hz 50/60 Technical features - Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
Type of data definition ml - Output for slave 0-10 V
Speed / min-1 1000 - Operation and alarm display
Power input / W 2880 - Input for sensor 0-10 V or 4-20 mA
Current draw / A 4.4 - External 24 V input (programming)
Max. back pressure / Pa 190 - External release input
Min. ambient temperature -25 - Alarm relay
/ °C - Integrated PID controller
Max. ambient 65 - Motor current limit
temperature - PFC, passive
/ °C - RS485 MODBUS RTU
ml = Max. load · me = Max. efficiency · fa = Running at free air - Soft start
cs = Customer specs · cu = Customer unit - Control input 0-10 VDC / PWM
Subject to alterations - Control interface with SELV potential
safely disconnected from the mains
3.3 Data according to ErP directive
- Over-temperature protected
Installation category A electronics / motor
Efficiency category Static - Line undervoltage / phase failure
Variable speed drive Yes detection
Specific ratio* 1.00 Touch current acc. <= 3.5 mA
* Specific ratio = 1 + pfs / 100 000 Pa IEC 60990 (measuring
network Fig. 4, TN
Actual Request Request
system)
2013 2015
Electrical leads Via terminal box
Overall efficiency ηes / % 44.5 32.6 36.6
Motor protection Reverse polarity and locked-rotor
Efficiency grade N 47.9 36 40
protection
Power input Ped / kW 2.93
Protection class I (if protective earth is connected by
Air flow qv / m³/h 22085
customer)
Pressure increase total psf / Pa 202
Product conforming EN 61800-5-1; CE
Speed n / min-1 1005
to standard
Data definition with optimum efficiency.
Approval C22.2 Nr.77 + CAN/CSA-E60730-1;
The ErP data is determined using a motor-impeller combination in a standardised
measurement configuration. EAC; UL 1004-7 + 60730
Translation of the original operating instructions

For cyclic speed loads, note that the rotating parts of the device
3.4 Technical features are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.
Mass 57 kg
Size 910 mm 3.5 Mounting data
Surface of rotor Coated in black
; Secure the mounting screws against accidentally coming loose (e.g.
Material of electronics Die-cast aluminium, coated in black
by using self-locking screws).
housing
Material of blades Aluminium sheet insert, sprayed with PP Strength class for 8.8
plastic mounting screws
Material of wall ring Sheet steel, pre-galvanised and coated in You can obtain additional mounting data from the product drawing if
black plastic (RAL 9005) necessary.
Material of guard grille Steel, coated in black plastic (RAL9005)
Number of blades 5
Blade angle 0°
Direction of air flow "V"
Direction of rotation Clockwise, seen on rotor
Type of protection IP 54
Insulation class "F"

Item no. 50276-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions

3.6 Transport and storage conditions 4. CONNECTION AND START-UP


; Use the device in accordance with its protection type.
4.1 Connecting the mechanical system
Max. permissible + 80 °C
ambient motor temp. CAUTION
(transp./ storage) Cutting and crushing hazard when removing the device
Min. permissible - 40 °C from the packaging
ambient motor temp. Blades can be bent
(transp./storage) → Carefully remove the device from its packaging, only
touching the wall ring. Make sure to avoid any shock.
3.7 Electromagnetic compatibility → Wear safety shoes and cut-resistant safety gloves.
EMC interference Acc. to EN 61000-6-2 (industrial CAUTION
immunity environment) Heavy load when taking out the device
EMC interference Acc. to EN 61000-6-3 (household Bodily harm, e.g. back injuries, are possible.
emission environment) → Two people should remove the device out of its packaging
together.
If several devices are switched in parallel on the mains side so
that the line current of the arrangement is in the range of 16 - 75 ; Check the device for transport damage. Damaged devices must no
A, then this arrangement conforms to IEC 61000-3-12 provided longer be installed.
that the short-circuit power Ssc at the connection point of the ; Install the undamaged device according to your application.
customer system to the public power system is greater than or
equal to 120 times the rated output of the arrangement. 4.2 Connecting the electrical system
It is the responsibility of the installation engineer or operator/
DANGER
owner of the device to ensure, if necessary after consultation
Electric voltage on the device
with the network operator, that this device is only connected to
Electric shock
a connection point with a Ssc value that is greater than or equal
to 120 times the rated output of the arrangement. → Always install a protective earth first.
→ Check the protective earth.
DANGER
Incorrect insulation
Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation
requirements for voltage, current, insulation material, load etc.
→ Route cables such that they cannot be touched by any
rotating parts.
DANGER
Electrical load (>50 µC) between mains wire and
protective earth connection after switching of the supply
when switching multiple devices in parallel.
Electric shock, risk of injury
Translation of the original operating instructions

→ Make sure that sufficient protection against accidental contact


is provided.
Before working on the electrical connection, the
connections to the mains supply and PE must be shorted.
CAUTION
Electrical voltage
The fan is a built-in component and features no electrically
isolating switch.
→ Only connect the fan to circuits that can be switched off with
an all-pole separating switch.
→ When working on the fan, you must switch off the
installation/machine in which the fan is installed and secure it
from being switched on again.
NOTE
Interferences and failures are possible
Maintain a distance to the power supply line when routing the
control lines of the device.

Item no. 50276-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 6 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions

→ Ensure a sufficiently large clearance. 4.2.3 Idle current


Recommendation: clearance > 10 cm (separate cable
routing) Because of the EMC filter integrated for compliance with EMC
limits (interference emission and interference immunity), idle
NOTE currents in the mains cable can be measured even when the
Water penetration into leads or wires motor is at a standstill and the mains voltage is switched on.
Water enters at the cable end on the customers side and can
● The values lie in a range of typical < 250 mA.
damage the device.
● The effective power in this operating state (readiness for operation) is
→ Make sure that the cable end is connected in a dry
simultaneously at typical < 5 W.
environment.
Connect the device only to circuits that can be switched off 4.2.4 Residual current operated device
using an all-pole disconnecting switch. Only universal (type B or B+) RCD protective devices are
permitted. Like frequency inverters, RCD protective devices
4.2.1 Prerequisites
cannot provide personal safety while operating the device.
; Check whether the data on the type plate agree with the connection When switching on the power supply of the device, pulsed
data. charge currents from the capacitors in the integrated EMC filter
; Before connecting the device, ensure that the supply voltage matches can lead to the RCD protective devices triggering without
the operating voltage of the device. delay. We recommend residual current devices with a trigger
threshold of 300 mA and delayed triggering (super-resistant,
; Only use cables designed for current according to the type plate.
characteristic K).
For determining the cross-section, follow the basic principles in
accordance with EN 61800-5-1. The protective earth must have a 4.2.5 Leakage current
cross-section equal to or greater than the outer conductor cross-
section. For asymmetrical power systems or if a phase fails, the
We recommend the use of 105°C cables. Ensure that the minimum leakage current can increase to a multiple of the nominal value.
cable cross-section is at least
AWG26/0.13 mm². 4.2.6 Locked-rotor protection

Earth wire contact resistance to EN 61800-5-1 Due to the locked-rotor protection, the start-up current (LRA) is
equal to or less than the nominal current (FLA).
Compliance with the impedance specifications to EN 61800-5-1 for the
protective earth circuit must be verified in the end application.
4.3 Connection in terminal box
Depending on the installation situation, it may be necessary to install an
additional protective earthing conductor via the additional protective earth
4.3.1 Preparing connection lines for the connection
connection point available on the device.
The protective earth connection point is located on the housing and has Strip the cable just enough so that the screwed cable gland is tight and
a protective earth symbol and a bore hole. the terminals are relieved of strain. Tightening torque, see chapter 3.1
Product drawing.
4.2.2 Power supply connection, fuse protection
Assignment of conductor cross-sections and the fuse protection required
for them (overload protection only, no device protection).
Nominal Safety Automatic Wire Wire
voltage fuse circuit cross- cross-
Translation of the original operating instructions

breaker section section


VDE UL VDE mm² *AWG
3/PE AC 16 A 15 A C16A 1.5 16
380 - 480
VAC
3/PE AC 20 A 20 A C20A 2.5 14
380 - 480
VAC Fig. 1: Recommended stripping lengths in mm (inside the terminal box)
3/PE AC 25 A 25 A C25A 4.0 12 Legend: CL = control lines
380 - 480
VAC
3/PE AC 32 A 30 A C32A 6.0 10
380 - 480
VAC
* AWG = American Wire Gauge

Item no. 50276-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 7 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions

4.3.2 Connecting cables with terminals 4.3.3 Cable routing


WARNING No water may penetrate along the cable in the direction of the cable gland.
Terminals and connections have voltage even with a Fans installed lying flat
unit that is shut off
Make sure that the cable is routed in the form of a loop (water trap).
Electric shock
→ Wait five minutes after disconnecting the voltage at all poles
before opening the device.
; Remove the cap from the screwed cable gland.
Remove the cap only in those places where cables are inserted.
; Mount the screwed cable glands with the seal inserts provided in the
terminal box.
; Insert the line(s) (not included in the standard scope of delivery) into
the terminal box.
; First connect the "PE" (protective earth) connection.
Fig. 3: Fan installed lying flat, cable routed as a water trap.
; Connect the lines to the corresponding terminals.
Use a screwdriver to do so. Fans installed in upright position
During the connection work, ensure that no cables splice off. When routing the cable, ensure that the screwed cable glands are
arranged at the bottom. The cables must always be routed downwards.

Fig. 4: Cable routing for fans installed upright.

4.4 Factory settings


Factory settings with which the device is pre-set by ebm-papst.
Translation of the original operating instructions

Control mode PWM controlling


parameter set 1
Control mode PWM controlling
parameter set 2
Fan / device adress 01
Max. PWM / % 100
Min. PWM / % 5
Save set value to Yes
Fig. 2: Connecting the wires to terminals
EEPROM
; Insert the strands until they meet resistance. Set value control Analogue (linear)
; Seal the terminal box. Control function Positive (heating)
parameter set 1
Control function Positive (heating)
parameter set 2

Item no. 50276-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 8 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions

4.5 Connection screen

No. Conn. Designation Function / assignment


KL 1 1 L1 Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz
KL 1 2 L2 Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz
KL 1 3 L3 Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz
PE PE Earth connection, PE connection
KL 2 1 NO Status relay, floating status contact; normally open; close with error
KL2 2 COM Status relay; floating status contact; changeover contact; common connection; contact rating 250 VAC / max.
2 A (AC1) / min. 10 mA
KL2 3 NC Status relay, floating status contact; break with error
KL 3 1 RSA Bus connection RS-485, RSA, MODBUS RTU; SELV
KL 3 2 RSB Bus connection RS-485, RSB, MODBUS RTU; SELV
KL 3 3 / 10 GND Signal ground for control interface; SELV
KL 3 4 Ain1 U Analogue input 1, set value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only usable as alternative to input
Ain1; SELV
KL 3 5 + 10 V Fixed voltage output 10 VDC, +10 V ±3%, max. 10 mA, short-circuit-proof, power supply for external
devices (e.g. potentiometer), SELV
KL 3 6 Ain1 I Analogue input 1, set value: 4-20 mA; Ri = 100 Ω, parametrisable curve, only usable as alternative to input
Ain1 U; SELV
KL 3 7 Din1 Digital input 1: enabling of electronics,
enabling: open pin or applied voltage 5-50 VDC
disabling: bridge to GND or applied voltage <1 VDC
Translation of the original operating instructions

reset function: triggers software reset after a level change to <1 VDC; SELV
KL 3 8 Din2 Digital input 2: parameter set switch 1/2, according to EEPROM setting, the valid/used parameter set can be
selected via bus or via digital input DIN2.
Parameter set 1: open pin or applied voltage 5-50 VDC
Parameter set 2: bridge to GND or applied voltage <1 VDC; SELV
KL 3 9 Din3 Digital input 3: controller function of integrated controller, according to EEPROM setting, the controller function
of the integrated controller is normally/inversely selectable per bus or per digital input
normal: open pin or applied voltage 5-50 VDC
inverse: bridge to GND or applied voltage <1 VDC; SELV
KL 3 11 Ain2 U Analogue input 2, actual value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only usable as alternative to input
Ain2; SELV
KL 3 12 + 20 V Fixed voltage output 20 VDC, +20 V +25/-10%, max. 50 mA, short-circuit-proof, power supply for external
devices (e.g. sensors); SELV
KL 3 13 Ain2 I Analogue input 2, actual value: 4-20 mA, Ri = 100 Ω, parametrisable curve, only usable as alternative to
input Ain2 U; SELV
KL 3 14 Aout Analogue output 0-10 VDC, max. 5 mA, output of the current motor level control coefficient / motor speed
parametrisable curve; SELV

Item no. 50276-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 9 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions

4.6 Checking the connections 5. INTEGRATED PROTECTIVE FUNCTIONS


; Make sure that the power is off (all phases). The integrated protective functions cause the motor to switch off
; Secure it from being switched on again. automatically in case of faults described in the table.
; Check the correct fit of the connection lines. Malfunctions Description / Function of
; Screw the terminal box cover closed again. Terminal box tightening safety feature
torque, see chapter 3.1 Product drawing. Rotor position detection error An automatic restart occurs.
; Route the connecting cables in the terminal box so that the terminal Locked rotor ; After the blockage is
box cover closes without resistance. removed, the motor restarts
; Use all plug screws (the entire number). In doing so, insert the automatically.
screws manually to avoid damage to the thread. Line under-voltage (mains input ; If the mains supply voltage
voltage outside of permitted returns to permitted values, the
; Make sure that the terminal box is correctly closed and sealed and
nominal voltage) motor restarts automatically.
that all screws and screwed cable glands are properly tightened.
Phase failure A phase of the supply voltage
4.7 Switch on device fails for at least 5 s.
; If all phases are correctly
The device may only be switched on if it has been installed properly and
supplied again, the motor
in accordance with its intended use, including the required safety
automatically restarts after 10 -
mechanisms and professional electrical connection. This also applies for
devices which have already been equipped with plugs and terminals or 40 s.
similar connectors by the customer.
WARNING
Hot motor housing
Fire hazard
→ Ensure that no combustible or flammable materials are
located close to the fan.
; Inspect the device for visible external damage and the proper function
of the protective features before switching it on.
; Check the air flow paths of the fan for foreign objects and remove any
that are found.
; Apply the nominal voltage to the voltage supply.
; Start the device by changing the input signal.

4.8 Switching off the device


Switching off the device during operation:
; Switch off the device via the control input.
; Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.
Switching off the device for maintenance work:
Translation of the original operating instructions

; Switch off the device via the control input.


; Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.
; Disconnect the device from the supply voltage.
; When disconnecting, be sure to disconnect the earth wire connection
last.

Item no. 50276-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 10 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions

6. MAINTENANCE, MALFUNCTIONS, POSSIBLE Insufficient cooling Improve cooling. Let


the device cool
CAUSES AND REMEDIES down.
Do not perform any repairs on your device. Return the device to ebm- To reset the error
papst for repair or replacement. message, switch off
WARNING the mains supply
Terminals and connections have voltage even with a voltage for a min. of
unit that is shut off 25 s and switch it on
Electric shock again.
→ Wait five minutes after disconnecting the voltage at all poles Alternatively, reset
before opening the device. the error message
by applying a control
CAUTION signal of <0.5 V to
If control voltage is applied or a speed setpoint is stored,
DIN1 or by short
the motor automatically restarts, e.g. after a power failure.
circuiting Din1 to
Danger of injury
GND.
→ Keep out of the danger zone of the device.
Ambient temperature Reduce the ambient
→ When working on the device, switch off the mains too high temperature. Let the
supply voltage and secure the latter from being switched on device cool down.
again. To reset the error
→ Wait until the device stops. message, switch off
→ After working on the device, remove any used tools or the mains supply
other objects from the device. voltage for a min. of
If the device remains out of use for over four months, we 25 s and switch it on
recommend switching the device on for at least three hours at again.
full speed to allow any condensate to evaporate and to move Alternatively, reset
the bearings. the error message
by applying a control
Malfunction/error Possible cause Possible remedy
signal of <0.5 V to
Impeller running Imbalance in rotating Clean the device; if
DIN1 or by short
roughly parts imbalance is still
circuiting Din1 to
evident after
GND.
cleaning, replace the
Unacceptable Correct the operating
device.
operating point (e.g. point. Let the device
If you have
counterpressure is cool down.
attached any weight
too high) To reset the error
clips during cleaning,
message, switch off
make sure to
the mains supply
remove them
voltage for a min. of
afterwards.
25 s and switch it on
Motor does not turn Mechanical blockage Switch off, de-
Translation of the original operating instructions

again.
energise, and
Alternatively, reset
remove mechanical
the error message
blockage.
by applying a control
Mains supply Check mains supply
signal of <0.5 V to
voltage faulty voltage,
DIN1 or by short
restore power
circuiting Din1 to
supply.
GND.
Important! The error
message resets If you have any other problems, contact ebm-papst.
automatically.
The device starts
up again
automatically without
advance warning.
Faulty connection De-energise, correct
connection, see
connection diagram.
Motor winding broken Replace device

Item no. 50276-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 11 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions

6.1 Cleaning
NOTE
Damage to the device during cleaning.
Malfunction possible
→ Do not clean the device using a water jet or high-pressure
washer.
→ Do not use any cleaners containing acids,
bases or solvents.
→ Do not use any pointed or sharp-edged objects to clean.

6.2 Safety test


NOTE
High-voltage test
The integrated EMC filter contains Y capacitors. Therefore, the
trigger current is exceeded when AC testing voltage is applied.
→ Test the device with DC voltage when you carry out the
high-voltage test required by law. The voltage to be used
corresponds to the peak value of the AC voltage required by
the standard.
What has to How to test? Frequency Which
be tested? measure?
Check the Visual inspection At least every Repair or
protective 6 months replacement of
casing against the device
accidental
contact for
damage and to
ensure that it is
intact
Check the Visual inspection At least every Replacement
device for 6 months of the device
damage to
blades and
housing
Mounting the Visual inspection At least every Fasten
connection lines 6 months
Check the Visual inspection At least every Replace wires
insulation of 6 months
the wires for
Translation of the original operating instructions

damage
Tightness of Visual inspection At least every Retighten,
screwed cable 6 months replace if
gland damaged
Condensate Visual inspection At least every Open bore holes
discharge 6 months
holes for
clogging, as
necessary
Weld seams Visual inspection At least every Replace device
for crack 6 months
formation

Item no. 50276-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 12 / 12