W3G910GV0201 Ba Eng
W3G910GV0201 Ba Eng
Operating instructions
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions
CAUTION WARNING
If control voltage is applied or a speed setpoint is stored, Rotating device
the motor automatically restarts, e.g. after a power failure. Long hair, loose items of clothing and jewellery could become
Danger of injury entangled and pulled into the device. You could be injured.
→ Keep out of the danger zone of the device. → Do not wear any loose clothing or jewellery while working
→ When working on the device, switch off the mains on rotating parts.
supply voltage and secure the latter from being switched on → Protect long hair by wearing a cap.
again.
→ Wait until the device stops.
1.8 Emission
→ After working on the device, remove any used tools or WARNING
other objects from the device. Depending on the installation and operating conditions,
a sound pressure level greater than 70 dB(A) may arise.
1.5 Safety and protective functions Danger of noise-induced hearing loss
DANGER → Take appropriate technical safety measures.
Missing safety device and non-functioning safety device → Protect operating personnel with appropriate safety
If there is no safety device, you could be seriously injured, for equipment, e.g. hearing protection.
example if you reach into the running device or your hands are → Also observe the requirements of local agencies.
sucked into it.
→ Operate the device only with a fixed and isolating safety 1.9 Hot surface
protection and a fixed guard grille.
CAUTION
The guard must withstand the kinetic energy of a fan blade
High temperature at the electronics enclosure
detaching at maximum speed.
Danger of burn injuries
→ The device is a built-in component. You, the owner/
→ Ensure that sufficient protection against accidental contact is
operator, are responsible for providing adequate protection for
provided.
the device.
→ Shut down the device immediately if you detect a 1.10 Transport
missing or ineffective protective feature.
WARNING
1.6 Electromagnetic radiation Transport of fan
Injuries from slipping or falling.
Interference from electromagnetic radiation is possible, e.g. in conjunction
with open and closed-loop control devices. → Only transport the fan in its original packaging. # Transport
If unacceptable emission intensities occur when the fan is installed, the fan "lying flat", in other words with the axis vertical.
appropriate shielding measures have to be taken by the user. → Secure the fan(s) so that nothing can slip or fall, for
example using a lashing strap.
NOTE
Electrical or electromagnetic interferences after 1.11 Storage
integrating the device in installations on the customer's
side. ; Store the device, partially or fully assembled, in a dry and
→ Verify that the entire setup is EMC compliant. weatherproof manner in the original packing in a clean environment.
; Protect the device from environmental impacts and dirt until the final
1.7 Mechanical movement installation.
Translation of the original operating instructions
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions
Improper use
Using the device in the following ways is particularly prohibited and
may cause hazards:
● Operating the device with an imbalance, e.g. caused by dirt deposits
or icing.
● Operation in medical equipment with a life-sustaining or lifesaving
function.
● Operation with external vibrations.
● Moving solids content in flow medium.
● Painting the device
● Connections (e.g. screws) coming loose during operation.
● Opening the terminal box during operation.
● Moving air that contains abrasive particles.
● Moving highly corrosive air, e.g. salt spray mist. Exceptions are
devices that are intended for salt spray mist and protected accordingly.
● Moving air that contains dust pollution, e.g. suctioning off saw dust.
● Operating the device close to flammable materials or components.
Translation of the original operating instructions
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions
3. TECHNICAL DATA
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions
For cyclic speed loads, note that the rotating parts of the device
3.4 Technical features are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.
Mass 57 kg
Size 910 mm 3.5 Mounting data
Surface of rotor Coated in black
; Secure the mounting screws against accidentally coming loose (e.g.
Material of electronics Die-cast aluminium, coated in black
by using self-locking screws).
housing
Material of blades Aluminium sheet insert, sprayed with PP Strength class for 8.8
plastic mounting screws
Material of wall ring Sheet steel, pre-galvanised and coated in You can obtain additional mounting data from the product drawing if
black plastic (RAL 9005) necessary.
Material of guard grille Steel, coated in black plastic (RAL9005)
Number of blades 5
Blade angle 0°
Direction of air flow "V"
Direction of rotation Clockwise, seen on rotor
Type of protection IP 54
Insulation class "F"
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions
Earth wire contact resistance to EN 61800-5-1 Due to the locked-rotor protection, the start-up current (LRA) is
equal to or less than the nominal current (FLA).
Compliance with the impedance specifications to EN 61800-5-1 for the
protective earth circuit must be verified in the end application.
4.3 Connection in terminal box
Depending on the installation situation, it may be necessary to install an
additional protective earthing conductor via the additional protective earth
4.3.1 Preparing connection lines for the connection
connection point available on the device.
The protective earth connection point is located on the housing and has Strip the cable just enough so that the screwed cable gland is tight and
a protective earth symbol and a bore hole. the terminals are relieved of strain. Tightening torque, see chapter 3.1
Product drawing.
4.2.2 Power supply connection, fuse protection
Assignment of conductor cross-sections and the fuse protection required
for them (overload protection only, no device protection).
Nominal Safety Automatic Wire Wire
voltage fuse circuit cross- cross-
Translation of the original operating instructions
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions
reset function: triggers software reset after a level change to <1 VDC; SELV
KL 3 8 Din2 Digital input 2: parameter set switch 1/2, according to EEPROM setting, the valid/used parameter set can be
selected via bus or via digital input DIN2.
Parameter set 1: open pin or applied voltage 5-50 VDC
Parameter set 2: bridge to GND or applied voltage <1 VDC; SELV
KL 3 9 Din3 Digital input 3: controller function of integrated controller, according to EEPROM setting, the controller function
of the integrated controller is normally/inversely selectable per bus or per digital input
normal: open pin or applied voltage 5-50 VDC
inverse: bridge to GND or applied voltage <1 VDC; SELV
KL 3 11 Ain2 U Analogue input 2, actual value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only usable as alternative to input
Ain2; SELV
KL 3 12 + 20 V Fixed voltage output 20 VDC, +20 V +25/-10%, max. 50 mA, short-circuit-proof, power supply for external
devices (e.g. sensors); SELV
KL 3 13 Ain2 I Analogue input 2, actual value: 4-20 mA, Ri = 100 Ω, parametrisable curve, only usable as alternative to
input Ain2 U; SELV
KL 3 14 Aout Analogue output 0-10 VDC, max. 5 mA, output of the current motor level control coefficient / motor speed
parametrisable curve; SELV
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions
again.
energise, and
Alternatively, reset
remove mechanical
the error message
blockage.
by applying a control
Mains supply Check mains supply
signal of <0.5 V to
voltage faulty voltage,
DIN1 or by short
restore power
circuiting Din1 to
supply.
GND.
Important! The error
message resets If you have any other problems, contact ebm-papst.
automatically.
The device starts
up again
automatically without
advance warning.
Faulty connection De-energise, correct
connection, see
connection diagram.
Motor winding broken Replace device
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GV02-01
Operating instructions
6.1 Cleaning
NOTE
Damage to the device during cleaning.
Malfunction possible
→ Do not clean the device using a water jet or high-pressure
washer.
→ Do not use any cleaners containing acids,
bases or solvents.
→ Do not use any pointed or sharp-edged objects to clean.
damage
Tightness of Visual inspection At least every Retighten,
screwed cable 6 months replace if
gland damaged
Condensate Visual inspection At least every Open bore holes
discharge 6 months
holes for
clogging, as
necessary
Weld seams Visual inspection At least every Replace device
for crack 6 months
formation
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com